KNX USB INTERFACE
PRODUCT DESCRIPTION – KNX USB INTERFACE BNUS-00/00.1
The KNX USB Interface connects a PC to an EIB/KNX system via a USB socket type A in the front and a USB interface extension cord, in order to configure, parameterize and commission the EIB/KNX installation as well as bus monitor using the ETS (ETS3 or later) software. The maximum communication distance is 5m between the PC and the communication interface.
Operating voltage: 21~ 30 V DC, via the EIB BUS
Current Consumption: Max. 12 mA
Power Consumption: Max. 360 mW
Dimensions: 18 x 20 x 77 mm
Maintained Time after power-off: 200 ms
Connections: EIB / KNX: Bus connecting terminal (black/red) PC-connection: Via USB socket type A, Max. cable length 5 m (standardized)
Temperature Range: Operation -5℃ ~ 45℃ Storage -25℃ ~ 55℃ Transport -25℃ ~70 ℃
FUNCTIONS:
> download the products database to the KNX devices by ETS.
> monitor the KNX bus telegrams.
> diagnose the KNX device.